120V 2000VA 1600W Double-Conversion Smart Online UPS - 5 Outlets, Card Slot, LCD, USB, DB9, 1U Rack
Model: SU2000LCD1U
- Offers network-grade protection against power failures and voltage fluctuations
- Zero transfer time between on-line and battery modes for uninterrupted operation
- NEMA 5-20P input and 5 NEMA 5-20R outlets arranged in 2 switched load banks
- Optional WEBCARDLX network interface required to use Auto Probe feature
- ENERGY STAR-certified to save electricity, lower costs, and protect the environment
Double-Conversion UPS Protects Equipment Against Damage, Downtime and Data Loss
This 100/120/127V 50/60 Hz on-line double-conversion UPS system maintains perfect output by converting AC input to DC, then reconverting UPS output to fully regulated sine wave AC with +/-3% voltage regulation in on-line and battery modes. Featuring 1600W capacity, 540 joules of surge suppression, true on-line operation with pure sine wave output and zero transfer time between on-line and battery modes, the SmartOnline® SU2000LCD1U provides the highest level of AC power protection and battery backup for network equipment in your small- to medium-size data center or computer room.
Individually Controllable Load Banks Let You Access and Control Outlets Remotely
Five NEMA 5-20R outlets are split into two switchable load banks, allowing you to reboot select components or shed loads remotely. This UPS is recommended for any application supported by in-rack IT equipment, including servers, switches, phone systems, kiosks and high-end engineering and A/V computer systems.
Reliable, Expandable Battery Backup Keeps You Operational Through Power Outages
The field-replaceable, hot-swappable internal battery provides 10 minutes of support at half load (800W) and three minutes at full load (1600W), keeping protected equipment operational through power failures. The intelligent battery management system with temperature-compensated charging extends battery life.
ENERGY STAR-Certified Economy Mode Helps You Save Money and Protect the Environment
By meeting strict EPA efficiency guidelines, this ENERGY STAR-certified UPS system helps you save money and energy. A power-saving Economy mode setting option offers enhanced efficiency and reduced BTU output when utility power is already high quality.
Set Output Frequency to Match That of Your Connected Equipment
Using the UPS in Frequency Conversion mode will correct or convert the incoming frequency of 50 Hz to output 60 Hz (and vice versa).
- Offers network-grade protection against power failures and voltage fluctuations
- Zero transfer time between on-line and battery modes for uninterrupted operation
- NEMA 5-20P input and 5 NEMA 5-20R outlets arranged in 2 switched load banks
- Optional WEBCARDLX network interface required to use Auto Probe feature
- ENERGY STAR-certified to save electricity, lower costs, and protect the environment
- Package Includes:
- SU2000LCD1U SmartOnline Double-Conversion UPS
- USB cable
- RS-232 cable
- Rack-mounting hardware
- Owner’s manual
- Energy Star rated - Yes
- Rackmountable - Yes
- ROHS Compliant - Yes
- Warranty - Yes
- Spec Sheet available - Yes
- Operating Temperature (Maximum): 104 F
- Operating Temperature (Minimum): 32 F
- Estimated Runtime: 3 minutes
- Estimated Runtime: 0.05 hours
- Certifications: CSA, FCC
- Number of Outlets: 5
- Rack Units (Height): 1
- AC Voltage: 120 Volts
- Current Draw: 20 Amps
- Shipping Depth (with packaging): 32.68 in
- Shipping Height (with packaging): 6.10 in
- Shipping Width (with packaging): 22.83 in
- Product Weight: 48.50 lbs
- Shipping Weight: 106.92 lbs
- Warranty (Length/Type): 2 Years
- Cord Length (in/mm): 72 in
- Depth: 27.95 in
- Height: 1.73 in
- Width: 17.32 in
- Active Power: 1600 Watt
- Rated input current (Maximum Load): 15.9A (100V); 14.7A (120V); 13.9A (127V)
- Nominal Input Voltage(s) Supported: 100V AC; 120V AC; 127V AC
- Nominal input voltage description: 120V factory default
- UPS input connection type: 5-20P
- Input Circuit Breakers: 20A
- Input Phase: Single-Phase
- Output Volt Amp Capacity (VA): 2000
- Output Capacity (kVA): 2
- Output Capacity Details: ON LINE MODE: Maximum output capacity is reduced to 1440 watts at 100V nominal; FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion mode (127/120V 960 watts / 100V 864 watts) OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 106-115% load for 1 minute; 116-130% load for 12 seconds; 131-149% for 2 seconds and >150% load for 0 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits)
- Power Factor: 0.80
- Crest Factor: 3:1
- Nominal Voltage details: 120V factory-default nominal voltage
- Frequency Compatibility: 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
- Frequency compatibility details: ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds +/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE: Output is regulated to +/-0.05Hz
- Output voltage regulation (line mode): +/- 3%
- Output voltage regulation (Economy line mode): +/- 10%
- Output voltage regulation (Battery mode): +/- 3%
- Load Management Receptacles: Two switchable NEMA 5-20R outlet banks (Bank 1: 2 outlets / Bank 2: 3 outlets)
- Output AC waveform (AC mode): Pure Sine wave
- Output AC waveform (battery mode): Pure Sine wave
- Nominal Output Voltage(s) Supported: 100V; 120V; 127V
- Output Receptacles: (5) 5-15/20R
- Individually Controllable Load Banks: Yes
- Battery Type: Valve Regulated Lead Acid (VRLA)
- Full Load Runtime (min.): 3 min. (1600w)
- Half Load Runtime (min.): 10 min. (800w)
- DC system voltage (VDC): 48
- Battery recharge rate (included batteries): Less than 8 hours recharge to 90% (typical, full load discharge)
- Battery replacement description: Hot-swappable, user replaceable batteries
- Front panel LCD display: Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, frequency, operating mode, alarm function and a variety of additional options (see manual)
- Switches: 2 switches control off/on power status and alarm-cancel operation; 2 additional scroll-down and scroll-up / select options enable LCD status viewing and configuration options
- Alarm cancel operation: Power-fail alarm can be temporarily silenced using alarm-cancel switch
- Audible Alarm: Audible alarm indicates UPS startup, power-failure, low-battery, overload and UPS fault conditions
- LED Indicators: Two front panel LEDs indicate AC Output status (green) and Shutdown / Fault condition (red)
- UPS AC suppression joule rating: 540
- UPS AC suppression response time: Instantaneous
- EMI / RFI AC noise suppression: Yes
- Cooling Method: Fan
- Included mounting accessory description: Includes 4 post rackmount installation accessories; Included mounting brackets support front-to-rear rail distances of 635 to 914mm
- Installation form factors supported with included accessories: 4 post 19 inch rackmount
- Minimum Required Rack Depth without External Battery Pack (cm): 79
- Storage Temperature Range: +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Relative Humidity: 5% to 95%, non-condensing
- AC mode BTU / hr. (full load): 606.5
- AC economy mode BTU / hr. (full load): 111.4
- Battery mode BTU / hr. (full load): 888.7
- AC Mode Efficiency Rating (100% Load): 90%
- AC economy mode efficiency rating (100% load): 98%
- Audible Noise: 65 dBA at 1m front side
- Operating Elevation (m): Up to 3000m
- Network Management Cards: WEBCARDLX
- Network monitoring port description: Supports detailed monitoring of UPS and site power conditions
- PowerAlert software: For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert
- Communications Cable: USB and RS232 cabling included
- WatchDog compatibility: Supports Watchdog application, OS and hard-reboot restart options for remote applications
- Communications interface: Contact closure; EPO (emergency power off); RS-232; Slot for SNMP/Web interface; USB (HID enabled)
- Transfer Time: Zero (0 milliseconds) in double-conversion mode; 4-7 milliseconds (AC to DC) / 4 milliseconds (DC to AC) economy mode
- Low voltage transfer to battery power (setpoint): 50
- High voltage transfer to battery power (setpoint): 150