Pro AV Catalog
Crestron Electronics, Inc. - GLA-DT-VS-2-W
Request Quote
All Products
crestron-electronics

Steinel DT VS 2 Dual Technology Dual Relay Wall Switch Vacancy Sensor, White

Series: GLA-DT-VS-2

Model: GLA-DT-VS-2-W

Part #: 6508674

  • PIR and 40kHz ultrasonic wall switch vacancy sensor
  • Trigger mode settings enable what sensing technologies are used to keep the load ON
  • Adjustable ultrasonic reach setting from 25% to 100%
  • Bi-level load switching (2 relays)
  • Line voltage lighting control (120/230/277VAC, 50/60Hz)
Compare
Project List
Product Info
Tech Specs
Related Products
Documents

A line voltage, two relay, Dual Technology (PIR and ultrasonic) wall switch vacancy sensor to control bi-level lighting in commercial spaces.

Overview:

As part of our endeavour to deliver professional lighting and control solutions for the entire enterprise, Crestron is pleased to offer STEINEL PROFESSIONAL products, which are available for sale through authorized Crestron Commercial Lighting system integrators.

Based in Germany, STEINEL PROFESSIONAL has been manufacturing lighting controls for over 25 years. Their product offering includes a wide variety of controls and sensors for indoor and outdoor applications.

The DT VS 2 is a line voltage, two relay, Dual Technology (PIR and ultrasonic) wall switch vacancy (manual ON) sensor intended to control bi-level lighting in commercial spaces. The combination of both technologies enhances occupancy detection in difficult applications. DIP switch adjustable technology options to initiate the load ON and maintain the load ON with either or both technologies. The convenient “Switch Link” feature enables up to four sensors to link together for peer to peer grouping achieving expanded detection zones and multiway switching.

The typical application is for bi-level switching in small offices, conference rooms or break rooms where vacancy control (manual ON only) is desired. For best performance use this sensor in enclosed spaces no larger than 20' x 16'.

  • PIR and 40kHz ultrasonic wall switch vacancy sensor
  • Trigger mode settings enable what sensing technologies are used to keep the load ON
  • Adjustable ultrasonic reach setting from 25% to 100%
  • Bi-level load switching (2 relays)
  • Line voltage lighting control (120/230/277VAC, 50/60Hz)
  • 180° Coverage pattern
  • Re-trigger feature allows the load to turn back ON automatically if motion is detected within 30 seconds after it has automatically switched OFF the load
  • Mounts to a single-gang NEMA-style, standard switch box and decorator-style wall plate by others
  • “Switch Link” communication allows for up to 4 sensors to be grouped together
  • Manual ON automatic OFF
  • IQ Mode dynamically adjusts the ‘ON’ time delay by learning individual room occupancy
  • Walk through mode option will switch the load OFF in 3 minutes if no additional detection occurs after the first 30 seconds
  • Audible alert feature provides an audible warning that the load will shut-OFF in 10 seconds unless additional motion is detected
  • Visible alert feature provides a momentary OFF/ON blink, warning that the load will shut OFF in 10 seconds unless additional motion is detected
  • Service mode option deactivates the automated functions of the sensor and the load is only manually controlled using the ON/OFF button
 
Request Quote